| Compliance List |
5 CSR 25-500.032 Organization and Administration
Compliance
|
5 CSR 25-500.042 Licensing Process
Compliance
|
5 CSR 25-500.052 Annual Requirements
Compliance
|
5 CSR 25-500.082 Physical Requirements of Group Day Care Homes and Day Care Centers
Violation
| | Provider Comments |
Violation The requirements for protective outlet covers or twist-lock outlets were not met as evidenced by electrical outlets were not covered in that two (2) outlets were not covered in the PreK classroom. Licensing Rule Reference 5 CSR 25-500.082 Physical Requirements of Group Day Care Homes and Day Care Centers (1) (G) states: Protective outlet covers or twist-lock outlets shall be used in areas accessible to the children. Correction Required The facility shall use outlet covers or twist-lock outlets as required.
Correction Verification Corrected on Site
Compliance Date 7/2/2024
|
|
Violation The ceilings located in the preschool room was/were not in good condition as evidenced by stained ceiling tiles in two (2) areas. Licensing Rule Reference 5 CSR 25-500.082 Physical Requirements of Group Day Care Homes and Day Care Centers (2) (A) 6. states: Walls, ceilings and floors shall be finished with material which can be cleaned easily and shall be free of splinters, cracks and chipping paint. Floor covering shall be in good condition. Lead-free paint shall be used for all painted surfaces. Correction Required Walls, ceilings, and floors shall be made of approved materials, easily cleaned and in good condition.
Correction Verification Submit Documentation
Compliance Date
|
|
Violation The facility did not have a fenced outdoor play area that was on or adjoining the day care property and was accessible without hazard as evidenced by the fence was not in good condition in that the wood fence was leaning in an area that was approximately 25-30 feet on the older preschool playground appearing to be unstable as I pushed on the fence giving 4 - 5 inches of sway. Licensing Rule Reference 5 CSR 25-500.082 Physical Requirements of Group Day Care Homes and Day Care Centers (6) (A) 1. states: A fenced outdoor play area shall be available on or adjoining the day care property. The play area shall be located so it is convenient and the children can gain access to it without hazard. For facilities initially licensed after the effective date of these rules or for the installation of new fences in existing facilities, the fence shall be at least forty-two inches (42") high. An outdoor play area used exclusively for school-age children shall not be required to have a fence. Fences shall be constructed to prevent children from crawling or falling through or becoming entrapped. Correction Required The outdoor play area shall be accessible without hazard.
Correction Verification Submit Documentation
Compliance Date
|
|
Violation The facility's outdoor space was not safe for children's activities as evidenced by peeling paint on the wood fence surrounding the air conditioning unit which also had protruding nails in multiple areas. Licensing Rule Reference 5 CSR 25-500.082 Physical Requirements of Group Day Care Homes and Day Care Centers (6) (A) 4. states: The play area shall be safe for children's activities, well-maintained, free of hazards such as poisonous plants, broken glass, rocks or other debris and shall have good drainage. Correction Required The outdoor play area shall be clean, safe and well-maintained as required.
Correction Verification Submit Documentation
Compliance Date
|
|
Violation The fall-zone area under and around outdoor equipment where children might fall and be injured was not covered with impact-absorbing materials to cushion a fall as evidenced by resilient material was not uniformly spread over the fall-zone area. Licensing Rule Reference 5 CSR 25-500.082 Physical Requirements of Group Day Care Homes and Day Care Centers (6) (A) 7. states: Areas under and around outdoor equipment shall have continuous maintenance to ensure that the material remains in place and retains its cushioning properties. The resilient material shall be supplemented immediately or replaced as needed. Correction Required The facility shall maintain approved resilient material in all fall-zone areas.
Correction Verification Submit Documentation
Compliance Date
|
|
Violation The floors located in the early preschool room was/were not clean as evidenced by the ABC large area rug had multiple dirt stains. Licensing Rule Reference 5 CSR 25-500.082 Physical Requirements of Group Day Care Homes and Day Care Centers (2) (A) 6. states: Walls, ceilings and floors shall be finished with material which can be cleaned easily and shall be free of splinters, cracks and chipping paint. Floor covering shall be in good condition. Lead-free paint shall be used for all painted surfaces. Correction Required Walls, ceilings, and floors shall be made of approved materials, easily cleaned and in good condition.
Correction Verification Submit Documentation
Compliance Date
|
|
Violation The walls located infant room was/were not finished with material which can be cleaned easily as evidenced by chipped paint was observed behind the rocking chair. Licensing Rule Reference 5 CSR 25-500.082 Physical Requirements of Group Day Care Homes and Day Care Centers (2) (A) 6. states: Walls, ceilings and floors shall be finished with material which can be cleaned easily and shall be free of splinters, cracks and chipping paint. Floor covering shall be in good condition. Lead-free paint shall be used for all painted surfaces. Correction Required Walls, ceilings, and floors shall be made of approved materials, easily cleaned and in good condition.
Correction Verification Submit Documentation
Compliance Date
|
|
Violation The walls located in the preschool room was/were not clean as evidenced by dirt and sticky paper residue was observed in the library area and the group time wall in the block area. Licensing Rule Reference 5 CSR 25-500.082 Physical Requirements of Group Day Care Homes and Day Care Centers (2) (A) 6. states: Walls, ceilings and floors shall be finished with material which can be cleaned easily and shall be free of splinters, cracks and chipping paint. Floor covering shall be in good condition. Lead-free paint shall be used for all painted surfaces. Correction Required Walls, ceilings, and floors shall be made of approved materials, easily cleaned and in good condition.
Correction Verification Submit Documentation
Compliance Date
|
|
Violation The walls located in the preschool room was/were not finished with material which can be cleaned easily as evidenced by chipped paint on the wall in the library area. Licensing Rule Reference 5 CSR 25-500.082 Physical Requirements of Group Day Care Homes and Day Care Centers (2) (A) 6. states: Walls, ceilings and floors shall be finished with material which can be cleaned easily and shall be free of splinters, cracks and chipping paint. Floor covering shall be in good condition. Lead-free paint shall be used for all painted surfaces. Correction Required Walls, ceilings, and floors shall be made of approved materials, easily cleaned and in good condition.
Correction Verification Submit Documentation
Compliance Date
|
|
Violation The walls located in the 2 year old room was/were not clean as evidenced by dirty walls by the area rug and the outside wall of the room. Licensing Rule Reference 5 CSR 25-500.082 Physical Requirements of Group Day Care Homes and Day Care Centers (2) (A) 6. states: Walls, ceilings and floors shall be finished with material which can be cleaned easily and shall be free of splinters, cracks and chipping paint. Floor covering shall be in good condition. Lead-free paint shall be used for all painted surfaces. Correction Required Walls, ceilings, and floors shall be made of approved materials, easily cleaned and in good condition.
Correction Verification Submit Documentation
Compliance Date
|
|
|
5 CSR 25-500.087 Fire Safety
Compliance
|
5 CSR 25-500.090 Disaster and Emergency Preparedness
Compliance
|
5 CSR 25-500.092 Furniture, Equipment and Materials
Violation
| | Provider Comments |
Violation The requirements for equipment to be clean, in good condition and accessible were not met as evidenced by sticky paper residue was observed on one (1) shelf in the preschool classroom by the door going outside. Licensing Rule Reference 5 CSR 25-500.092 Furniture, Equipment and Materials (2) (A) 1. states: Play equipment and materials shall be clean, in good condition with all parts intact and accessible to children. Correction Required Indoor play equipment, clean and in good repair, shall be accessible to children.
Correction Verification Submit Documentation
Compliance Date
|
|
|
5 CSR 25-500.102 Personnel
Compliance
|
5 CSR 25-500.112 Staff/Child Ratios
Compliance
|
5 CSR 25-500.122 Medical Examination Reports
Compliance
|
5 CSR 25-500.132 Admission Policies and Procedures
Violation
| | Provider Comments |
Violation An individualized plan for specialized care for a child with special physical, developmental or behavioral needs was not on file. Licensing Rule Reference 5 CSR 25-500.132 Admission Policies and Procedures (6) states: A child who has a special physical, developmental or behavioral need shall have on file an individualized plan for specialized care from a professionally qualified source. Correction Required An individualized plan from a professional source shall be on file as required.
Correction Verification Submit Documentation
Compliance Date
|
|
|
5 CSR 25-500.142 Nighttime Care
Compliance
|
5 CSR 25-500.162 Overlap Care of Children
Compliance
|
5 CSR 25-500.172 Emergency School Closings
Compliance
|
5 CSR 25-500.182 Child Care Program
Compliance
|
5 CSR 25-500.192 Health Care
Compliance
|
5 CSR 25-500.202 Nutrition and Food Service
Compliance
|
5 CSR 25-500.212 Transportation and Field Trips
Compliance
|
5 CSR 25-500.222 Records and Reports
Violation
| | Provider Comments |
Violation One (1) child(ren) records did not include full name, home address, employers name and address, work schedule and home and work telephone numbers of the parent(s), guardian or legal custodian. Licensing Rule Reference 5 CSR 25-500.222 Records and Reports (2) (B) states: Full name of the parent(s), guardian or legal custodian, home address, employers' name and address, work schedule, and home and work telephone numbers; Correction Required Child enrollment information shall be completed and on file as required.
Correction Verification Corrected on Site
Compliance Date 7/2/2024
|
|
Violation One (1) child(ren) records did not include address of another individual who might be reached in an emergency. Licensing Rule Reference 5 CSR 25-500.222 Records and Reports (2) (C) states: Name, address and telephone number of another individual (friend or relative) who might be reached in an emergency when the parent(s), guardian or legal custodian cannot be reached; Correction Required Child enrollment information shall be completed and on file as required.
Correction Verification Corrected on Site
Compliance Date 7/2/2024
|
|
|
5 CSR 25-600.020 General Requirements
Compliance
|
5 CSR 25-600.040 Background Screening Findings
Compliance
|
RSMo 210.115. Reports of abuse, neglect, and under age eighteen deaths — persons required to report — supervisors and administrators not to impede reporting — deaths required to be reported to the division or child fatality review panel, when — report made to another state, when. —
Compliance
|
RSMo 210.211. License required - exceptions - written notice of licensure status, when.
Compliance
|