| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| General Requirements.
(D) The department shall have the right of inspection of any portion of a building in which a licensed facility is located unless the unlicensed portion is separated by two- (2-) hour fire-resistant construction. No section of the building shall present a fire hazard. I/II
|
4/18/2019
| | |
| Fire Safety Training Requirements.
(A) The facility shall ensure that fire safety training is provided to all employees:
1. During employee orientation;
2. At least every six (6) months; and
3. When training needs are identified as a result of fire drill evaluations. II/III
|
4/18/2019
| | |
| Complete Fire Alarm Systems.
(A) All facilities shall have a complete fire alarm system installed in accordance with NFPA 101, Section 18.3.4, 2000 edition. The complete fire alarm shall automatically transmit to the fire department, dispatching agency, or central monitoring company. The complete fire alarm system shall include visual signals and audible alarms that can be heard throughout the building and a main panel that interconnects all alarm-activating devices and audible signals. Manual pull stations shall be installed at or near each required attendant ' s station and each required exit. I/II
|
4/18/2019
| | |
| Complete Fire Alarm Systems.
(C) All facilities shall test and maintain the complete fire alarm system in accordance with NFPA 72, 1999 edition. I/II
|
4/18/2019
| | |
| Protection from Hazards.
(A) In assisted living facilities and residential care facilities licensed on or after November 13, 1980, for more than twelve (12) beds, hazardous areas shall be separated by construction of at least a one- (1-) hour fire-resistant rating. In facilities equipped with a complete fire alarm system, the one- (1-) hour fire separation is required only for furnace or boiler rooms. Hazardous areas equipped with a complete sprinkler system are not required to have this one- (1-) hour fire separation. Doors to hazardous areas shall be self-closing and shall be kept closed unless an electromagnetic hold-open device is used which is interconnected with the fire alarm system. When the sprinkler option is chosen, the areas shall be separated from other spaces by smoke-resistant partitions and doors. The doors shall be self-closing or automatic-closing. Facilities formerly licensed as residential care facility I or II, and existing prior to November 13, 1980, shall be exempt from this requirement. II
|
4/18/2019
| | |
| Protection from Hazards.
(I) In facilities whose plans were approved or which were initially licensed after December 31, 1987, for more than twenty (20) beds and all facilities licensed after August 28, 2007, each smoke section shall be separated by one- (1-) hour fire-rated smoke partitions. The smoke partitions shall be continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least twenty- (20-) minute fire-rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the complete fire alarm system. II
|
4/18/2019
| | |
| Sprinkler Systems.
(D) Single-story assisted living facilities that provide care to one (1) or more residents with a physical, cognitive, or other impairment that prevents the individual from safely evacuating the facility with minimal assistance shall install and maintain an approved sprinkler system in accordance with NFPA 13R, 1999 edition. I/II
|
4/18/2019
| | |
| Trash and Rubbish Disposal.
(A) Only metal or UL- or FM-fire-resistant rated wastebaskets shall be used for trash. II
|
4/18/2019
| | |
| The building shall be substantially constructed and shall be maintained in good repair and in accordance with the construction and fire safety rules in effect at the time of initial licensing. II/III
|
4/18/2019
| | |
| In newly licensed facilities or if a new heating system is installed in an existing licensed facility, the heating of the building shall be restricted to steam, hot water, permanently installed electric heating devices or a warm air system employing central heating plants with installation such as to safeguard the inherent fire hazard, or approved installation of outside wall heaters which bear the approved label of the American Gas Association or National Board of Fire Underwriters. The foregoing requirements are applicable to residential care facilities. In assisted living facilities, the heating of the building shall be restricted to steam, hot water, permanently installed electric heating devices or a warm air system employing central heating plants with installation such as to safeguard the inherent fire hazard, or approved installation of outside wall heaters which bear the approved label of the American Gas Association or National Board of Fire Underwriters. For all facilities, oil or gas heating appliances shall be properly vented to the outside and the use of portable heaters of any kind is prohibited. If approved wall heaters are used, adequate guards shall be provided to safeguard residents. I/II
|
4/18/2019
| | |
| In facilities that are constructed or have plans approved after July 1, 2005, electrical wiring shall be installed and maintained in accordance with the requirements of the National Electrical Code, 1999 edition, National Fire Protection Association, Inc., incorporated by reference, in this rule and available by mail at One Batterymarch Park, Quincy, MA 02269, and local codes. This rule does not incorporate any subsequent amendments or additions to the materials incorporated by reference. Facilities built between September 28, 1979 and July 1, 2005 shall be maintained in accordance with the requirements of the National Electrical Code, which was in effect at the time of the original plan approval and local codes. This rule does not incorporate any subsequent amendments or additions. In facilities built prior to September 28, 1979, electrical wiring shall be maintained in good repair and shall not present a safety hazard. All facilities shall have wiring inspected every two (2) years by a qualified electrician. II/III
|
4/18/2019
| | |