| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| General Requirements.
(H) Facilities shall not use space under stairways to store combustible materials. I/II
|
10/13/2023
| | |
| General Requirements.
(H) Facilities shall not use space under stairways to store combustible materials. I/II
|
10/13/2023
| | |
| Range Hood Extinguishing Systems.
(C) The range hood and its extinguishing system shall be certified at least twice annually in accordance with NFPA 96, 1998 edition. II/III
|
10/13/2023
| | |
| Range Hood Extinguishing Systems.
(C) The range hood and its extinguishing system shall be certified at least twice annually in accordance with NFPA 96, 1998 edition. II/III
|
10/13/2023
| | |
| Fire Drills and Emergency Preparedness.
(D) A minimum of twelve (12) fire drills shall be conducted annually with at least one (1) every three (3) months on each shift. At least four (4) of the required fire drills must be unannounced to residents and staff, excluding staff who are assigned to evaluate staff and resident response to the fire drill. The fire drills shall include a resident evacuation at least once a year. II/III
|
10/13/2023
| | |
| Fire Drills and Emergency Preparedness.
(D) A minimum of twelve (12) fire drills shall be conducted annually with at least one (1) every three (3) months on each shift. At least four (4) of the required fire drills must be unannounced to residents and staff, excluding staff who are assigned to evaluate staff and resident response to the fire drill. The fire drills shall include a resident evacuation at least once a year. II/III
|
10/13/2023
| | |
| Complete Fire Alarm Systems.
(E) Facilities shall test by activating the complete fire alarm system at least once a month. I/II
|
10/13/2023
| | |
| Complete Fire Alarm Systems.
(E) Facilities shall test by activating the complete fire alarm system at least once a month. I/II
|
10/13/2023
| | |
| Protection from Hazards.
(I) In facilities whose plans were approved or which were initially licensed after December 31, 1987, for more than twenty (20) beds and all facilities licensed after August 28, 2007, each smoke section shall be separated by one- (1-) hour fire-rated smoke partitions. The smoke partitions shall be continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least twenty- (20-) minute fire-rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the complete fire alarm system. II
|
3/5/2024
| | |
| Protection from Hazards.
(I) In facilities whose plans were approved or which were initially licensed after December 31, 1987, for more than twenty (20) beds and all facilities licensed after August 28, 2007, each smoke section shall be separated by one- (1-) hour fire-rated smoke partitions. The smoke partitions shall be continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least twenty- (20-) minute fire-rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the complete fire alarm system. II
|
3/5/2024
| | |
| Sprinkler Systems.
(B) Facilities that have a sprinkler system installed prior to August 28, 2007, shall inspect, maintain, and test these systems in accordance with the requirements that were in effect for such facilities on August 27, 2007. I/II
|
10/13/2023
| | |
| Sprinkler Systems.
(B) Facilities that have a sprinkler system installed prior to August 28, 2007, shall inspect, maintain, and test these systems in accordance with the requirements that were in effect for such facilities on August 27, 2007. I/II
|
10/13/2023
| | |
| Emergency Lighting.
(C) If battery-powered lights are used, they shall be capable of operating the light for at least one and one-half (1 1/2) hours. II
|
10/13/2023
| | |
| Emergency Lighting.
(C) If battery-powered lights are used, they shall be capable of operating the light for at least one and one-half (1 1/2) hours. II
|
10/13/2023
| | |
| The building shall be substantially constructed and shall be maintained in good repair and in accordance with the construction and fire safety rules in effect at the time of initial licensing. II/III
|
10/13/2023
| | |
| The building shall be substantially constructed and shall be maintained in good repair and in accordance with the construction and fire safety rules in effect at the time of initial licensing. II/III
|
10/13/2023
| | |
| Rooms shall be neat, orderly and cleaned daily. II/III
|
10/13/2023
| | |
| Rooms shall be neat, orderly and cleaned daily. II/III
|
10/13/2023
| | |