| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| |
| | |
| |
| | |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Exit Signage
2012 EXISTING
Exit and directional signs are displayed in accordance with 7.10 with continuous illumination also served by the emergency lighting system.
19.2.10.1
(Indicate N/A in one-story existing occupancies with less than 30 occupants where the line of exit travel is obvious.) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Exit Signage
2012 EXISTING
Exit and directional signs are displayed in accordance with 7.10 with continuous illumination also served by the emergency lighting system.
19.2.10.1
(Indicate N/A in one-story existing occupancies with less than 30 occupants where the line of exit travel is obvious.) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Exit Signage
2012 EXISTING
Exit and directional signs are displayed in accordance with 7.10 with continuous illumination also served by the emergency lighting system.
19.2.10.1
(Indicate N/A in one-story existing occupancies with less than 30 occupants where the line of exit travel is obvious.) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Exit Signage
2012 EXISTING
Exit and directional signs are displayed in accordance with 7.10 with continuous illumination also served by the emergency lighting system.
19.2.10.1
(Indicate N/A in one-story existing occupancies with less than 30 occupants where the line of exit travel is obvious.) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Exit Signage
2012 EXISTING
Exit and directional signs are displayed in accordance with 7.10 with continuous illumination also served by the emergency lighting system.
19.2.10.1
(Indicate N/A in one-story existing occupancies with less than 30 occupants where the line of exit travel is obvious.) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Exit Signage
2012 EXISTING
Exit and directional signs are displayed in accordance with 7.10 with continuous illumination also served by the emergency lighting system.
19.2.10.1
(Indicate N/A in one-story existing occupancies with less than 30 occupants where the line of exit travel is obvious.) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Exit Signage
2012 EXISTING
Exit and directional signs are displayed in accordance with 7.10 with continuous illumination also served by the emergency lighting system.
19.2.10.1
(Indicate N/A in one-story existing occupancies with less than 30 occupants where the line of exit travel is obvious.) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Exit Signage
2012 EXISTING
Exit and directional signs are displayed in accordance with 7.10 with continuous illumination also served by the emergency lighting system.
19.2.10.1
(Indicate N/A in one-story existing occupancies with less than 30 occupants where the line of exit travel is obvious.) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Portable Fire Extinguishers
Portable fire extinguishers are selected, installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
18.3.5.12, 19.3.5.12, NFPA 10 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Portable Fire Extinguishers
Portable fire extinguishers are selected, installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
18.3.5.12, 19.3.5.12, NFPA 10 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Portable Fire Extinguishers
Portable fire extinguishers are selected, installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
18.3.5.12, 19.3.5.12, NFPA 10 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Portable Fire Extinguishers
Portable fire extinguishers are selected, installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
18.3.5.12, 19.3.5.12, NFPA 10 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Portable Fire Extinguishers
Portable fire extinguishers are selected, installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
18.3.5.12, 19.3.5.12, NFPA 10 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Portable Fire Extinguishers
Portable fire extinguishers are selected, installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
18.3.5.12, 19.3.5.12, NFPA 10 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Portable Fire Extinguishers
Portable fire extinguishers are selected, installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
18.3.5.12, 19.3.5.12, NFPA 10 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Portable Fire Extinguishers
Portable fire extinguishers are selected, installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
18.3.5.12, 19.3.5.12, NFPA 10 |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
4/1/2019
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Oxygen storage shall be in accordance with NFPA 99, 1999 edition. Facilities shall use permanent racks or fasteners to prevent accidental damage or dislocation of oxygen cylinders. Safety caps shall remain intact except where a cylinder is in actual use or where the regulator has been attached and the cylinder is ready for use. Individual oxygen cylinders in use or with an attached regulator shall be supported by cylinder collars or by stable cylinder carts. II/III
|
4/1/2019
| | |
| Fire Extinguishers.
(D) All fire extinguishers shall bear the label of the UL or the FM Laboratories and shall be installed and maintained in accordance with NFPA 10, 1998 edition. This includes the documentation and dating of a monthly pressure check. II/III
|
4/1/2019
| | |
| Each floor of an existing licensed facility shall have at least two (2) unobstructed exits remote from each other. One (1) of the required exits in an existing multi-story facility must be an outside stairway or an enclosed stair that is separated by one- (1-) hour construction from each floor and has an exit leading directly outside at grade level. One (1) exit may lead to a lobby with exit facilities to the ground level outside instead of leading directly to the outside. The lobby shall have at least a one- (1-) hour fire-rated separation from the remainder of the exiting floor. I/II
|
4/1/2019
| | |
| Facilities shall place signs bearing the word EXIT in plain, legible block letters at each required exit, except at doors directly from rooms to exit corridors or passageways. II
|
4/1/2019
| | |