Inspection Results
-
Facility failed to meet the following Requirement(s):Corrected DateLevel of HarmResidents Affected
Exit Signs. (C) All required exit signs and directional indicators shall be positioned so that both normal and emergency lighting illuminates them. II/III 10/15/2025   
Complete Fire Alarm Systems. (B) Facilities that are required to install a sprinkler system in accordance with section (11) of this rule shall comply with the following requirements: 1. Until the required sprinkler system is installed, each resident room or any room designated for sleeping shall be equipped with at least one (1) battery-powered smoke alarm installed, tested, and maintained in accordance with manufacturer ' s specifications. In addition, the facility shall be equipped with interconnected heat detectors installed, tested, and maintained in accordance with NFPA 72, 1999 edition, with detectors in all areas subject to nuisance alarms, including, but not limited to, kitchens, laundries, bathrooms, mechanical air handling rooms, and attic spaces. I/II B. Upon discovery of a fault with any detector or alarm, the facility shall correct the fault. I/II 10/15/2025   
Sprinkler Systems. (F) All facilities shall have inspections and written certifications of the approved sprinkler system completed by an approved qualified service representative in accordance with NFPA 25, 1998 edition. The inspections shall be in accordance with the provisions of NFPA 25, 1998 edition, with certification at least annually by a qualified service representative. I/II 10/15/2025