Inspection Results
-
Facility failed to meet the following Requirement(s):Corrected DateLevel of HarmResidents Affected
General Requirements. (D) The department shall have the right of inspection of any portion of a building in which a licensed facility is located unless the unlicensed portion is separated by two- (2-) hour fire-resistant construction. No section of the building shall present a fire hazard. I/II 2/4/2019   
Range Hood Extinguishing Systems. (B) In licensed facilities with a total of twenty-one (21) or more licensed beds and whose application was filed after July 11, 1980, and prior to October 1, 2000: 1. The kitchen shall be provided with a range hood and an approved automatic range hood extinguishing system unless the facility has an approved sprinkler system. Facilities with range hood systems shall continue to maintain and test these systems; and 2. The extinguishing system shall be installed, tested, and maintained in accordance with NFPA 96, 1998 edition. II/III 2/4/2019   
Complete Fire Alarm Systems. (C) All facilities shall test and maintain the complete fire alarm system in accordance with NFPA 72, 1999 edition. I/II 2/4/2019   
Protection from Hazards. (C) Electric or gas clothes dryers shall be vented to the outside. Lint traps shall be cleaned regularly to protect against fire hazard. II/III 2/4/2019   
Sprinkler Systems. (B) Facilities that have a sprinkler system installed prior to August 28, 2007, shall inspect, maintain, and test these systems in accordance with the requirements that were in effect for such facilities on August 27, 2007. I/II 2/4/2019