| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| |
| | |
| |
| | |
| |
| | |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 EXISTING
Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier.
19.3.7.3, 8.6.7.1(1)
Describe any mechanical smoke control system in REMARKS. |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 EXISTING
Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier.
19.3.7.3, 8.6.7.1(1)
Describe any mechanical smoke control system in REMARKS. |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 EXISTING
Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier.
19.3.7.3, 8.6.7.1(1)
Describe any mechanical smoke control system in REMARKS. |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 EXISTING
Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier.
19.3.7.3, 8.6.7.1(1)
Describe any mechanical smoke control system in REMARKS. |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 EXISTING
Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier.
19.3.7.3, 8.6.7.1(1)
Describe any mechanical smoke control system in REMARKS. |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 EXISTING
Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier.
19.3.7.3, 8.6.7.1(1)
Describe any mechanical smoke control system in REMARKS. |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 EXISTING
Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier.
19.3.7.3, 8.6.7.1(1)
Describe any mechanical smoke control system in REMARKS. |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 EXISTING
Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier.
19.3.7.3, 8.6.7.1(1)
Describe any mechanical smoke control system in REMARKS. |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9 |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) |
7/23/2021
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Some |
| Oxygen storage shall be in accordance with NFPA 99, 1999 edition. Facilities shall use permanent racks or fasteners to prevent accidental damage or dislocation of oxygen cylinders. Safety caps shall remain intact except where a cylinder is in actual use or where the regulator has been attached and the cylinder is ready for use. Individual oxygen cylinders in use or with an attached regulator shall be supported by cylinder collars or by stable cylinder carts. II/III
|
7/23/2021
| | |
| Door locks shall be of a type that can be opened from the inside by turning the knob or operating a simple device that will release the lock, or shall meet the requirements of Section 19.2 of NFPA 101, 2000 edition. Only one (1) lock will be permitted on any one (1) door. I/II
|
7/23/2021
| | |
| Door locks shall be of a type that can be opened from the inside by turning the knob or operating a simple device that will release the lock, or shall meet the requirements of Section 19.2 of NFPA 101, 2000 edition. Only one (1) lock will be permitted on any one (1) door. I/II
|
7/23/2021
| | |
| Each smoke section shall be separated by one- (1-) hour fire-rated walls that are continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least twenty- (20-) minute fire rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the fire alarm system. II
|
7/23/2021
| | |