| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| Complete Fire Alarm Systems.
(H) When a complete fire alarm system is to be out-of- service for more than four (4) hours in a twenty-four- (24-) hour period, the facility shall immediately notify the department and the local fire authority and implement an approved fire watch in accordance with NFPA 101, 2000 edition, until the complete fire alarm system has returned to full service. I/II
|
10/5/2023
| | |
| Protection from Hazards.
(B) The storage of unnecessary combustible materials in any part of a building in which a licensed facility is located is prohibited. I/II
|
10/5/2023
| | |
| Protection from Hazards.
(I) In facilities whose plans were approved or which were initially licensed after December 31, 1987, for more than twenty (20) beds and all facilities licensed after August 28, 2007, each smoke section shall be separated by one- (1-) hour fire-rated smoke partitions. The smoke partitions shall be continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least twenty- (20-) minute fire-rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the complete fire alarm system. II
|
10/5/2023
| | |
| Emergency Lighting.
(C) If battery-powered lights are used, they shall be capable of operating the light for at least one and one-half (1 1/2) hours. II
|
10/5/2023
| | |
| Oxygen storage shall be in accordance with NFPA 99, 1999 Edition. II/III
|
10/5/2023
| | |
| The building shall be substantially constructed and shall be maintained in good repair and in accordance with the construction and fire safety rules in effect at the time of initial licensing. II/III
|
10/5/2023
| | |
| In facilities that are constructed or have plans approved after July 1, 2005, electrical wiring shall be installed and maintained in accordance with the requirements of the National Electrical Code, 1999 edition, National Fire Protection Association, Inc., incorporated by reference, in this rule and available by mail at One Batterymarch Park, Quincy, MA 02269, and local codes. This rule does not incorporate any subsequent amendments or additions to the materials incorporated by reference. Facilities built between September 28, 1979 and July 1, 2005 shall be maintained in accordance with the requirements of the National Electrical Code, which was in effect at the time of the original plan approval and local codes. This rule does not incorporate any subsequent amendments or additions. In facilities built prior to September 28, 1979, electrical wiring shall be maintained in good repair and shall not present a safety hazard. All facilities shall have wiring inspected every two (2) years by a qualified electrician. II/III
|
10/5/2023
| | |