| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| Fire Drills and Emergency Preparedness.
(B) The plan shall include, but is not limited to, the following:
1. A phased response ranging from relocation of residents to an immediate area within the facility; relocation to an area of refuge, if applicable; or to total building evacuation. This phased response part of the plan shall be consistent with the direction of the local fire unit or state fire marshal and appropriate for the fire or emergency;
2. Written instructions for evacuation of each floor including evacuation to areas of refuge, if applicable, and a floor plan showing the location of exits, fire alarm pull stations, fire extinguishers, and any areas of refuge;
3. Evacuating residents, if necessary, from an area of refuge to a point of safety outside the building;
4. The location of any additional water sources on the property such as cisterns, wells, lagoons, ponds, or creeks;
5. Procedures for the safety and comfort of residents evacuated;
6. Staffing assignments;
7. Instructions for staff to call the fire department or other outside emergency services;
8. Instructions for staff to call alternative resource(s) for housing residents, if necessary;
9. Administrative staff responsibilities; and
10. Designation of a staff member to be responsible for accounting for all residents ' whereabouts. II/III
|
5/21/2024
| | |
| Complete Fire Alarm Systems.
(A) All facilities shall have a complete fire alarm system installed in accordance with NFPA 101, Section 18.3.4, 2000 edition. The complete fire alarm shall automatically transmit to the fire department, dispatching agency, or central monitoring company. The complete fire alarm system shall include visual signals and audible alarms that can be heard throughout the building and a main panel that interconnects all alarm-activating devices and audible signals. Manual pull stations shall be installed at or near each required attendant ' s station and each required exit. I/II
|
5/21/2024
| | |
| Protection from Hazards.
(I) In facilities whose plans were approved or which were initially licensed after December 31, 1987, for more than twenty (20) beds and all facilities licensed after August 28, 2007, each smoke section shall be separated by one- (1-) hour fire-rated smoke partitions. The smoke partitions shall be continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least twenty- (20-) minute fire-rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the complete fire alarm system. II
|
5/21/2024
| | |
| Trash and Rubbish Disposal.
(A) Only metal or UL- or FM-fire-resistant rated wastebaskets shall be used for trash. II
|
5/21/2024
| | |
| If extension cords are used, they must be Underwriters ' Laboratory (UL)-approved or shall comply with other recognized electrical appliance approval standards and sized to carry the current required for the appliance used. Only one (1) appliance shall be connected to one (1) extension cord and only two (2) appliances may be served by one (1) duplex receptacle. If extension cords are used, they shall not be placed under rugs, through doorways or located where they are subject to physical damage. II/III
|
5/21/2024
| | |