Inspection Results
-
Facility failed to meet the following Requirement(s):Corrected DateLevel of HarmResidents Affected
Residential care facilities and facilities formerly licensed as residential care facilities II whose plans were initially approved between December 31, 1987 and December 31, 1998, shall have at least one (1) hydraulic or electric motor-driven elevator if there are more than twenty (20) residents with bedrooms above the first floor. The elevator installation(s) shall comply with all local and state codes, American Society for Mechanical Engineers (ASME) A17.1, Safety Code for Elevators, Dumbwaiters, and Escalators, and the National Fire Protection Association ' s applicable codes. All facilities with plans approved on or after January 1, 1999, shall comply with all local and state codes, ASME A17.1, 1993 Safety Code for Elevators and Escalators, and the 1996 National Electrical Code. These references are incorporated by reference in this rule and available at: American Society for Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990; and The American National Standards Institute, 11 West 42nd Street, 13th Floor, New York, NY 10036. This rule does not incorporate any additional amendments or additions. II 11/8/2021   
Fire Drills and Emergency Preparedness. (D) A minimum of twelve (12) fire drills shall be conducted annually with at least one (1) every three (3) months on each shift. At least four (4) of the required fire drills must be unannounced to residents and staff, excluding staff who are assigned to evaluate staff and resident response to the fire drill. The fire drills shall include a resident evacuation at least once a year. II/III 11/8/2021   
Exits, Stairways, and Fire Escapes. (D) An " area of refuge " shall have- 1. An area separated by one- (1-) hour rated smoke walls, from the remainder of the building. This area must have direct access to the exit stairway or access the stair through a section of the corridor that is separated by smoke walls from the remainder of the building. This area may include no more than two (2) resident rooms; 2. A two- (2-) way communication or intercom system with both visible and audible signals between the area of refuge and the bottom landing of the exit stairway, attendants ' work area, or other primary location as designated in the written plan for fire drills and evacuation; 3. Instructions on the use of the area during emergency conditions that are located in the area of refuge and conspicuously posted adjoining the communication or intercom system; 4. A sign at the entrance to the room that states " AREA OF REFUGE IN CASE OF FIRE " and displays the international symbol of accessibility; 5. An entry or exit door that is at least a one and three-fourths inch (1 3/4") solid core wood door or has a fire protection rating of not less than twenty (20) minutes with smoke seals and positive latching hardware. These doors shall not be lockable; 6. A sign conspicuously posted at the bottom of the exit stairway with a diagram showing each location of the areas of refuge; 7. Emergency lighting for the area of refuge; and 8. The total area of the areas of refuge on a floor shall equal at least twenty (20) square feet for each resident who is blind or requires the use of a wheelchair or walker housed on the floor. II 11/8/2021   
Complete Fire Alarm Systems. (E) Facilities shall test by activating the complete fire alarm system at least once a month. I/II 11/8/2021   
Protection from Hazards. (F) Atriums open between floors will be permitted if resident room corridors are separated from the atrium by one- (1-) hour rated smoke walls. These corridors must have access to at least one (1) of the required exits without traversing any space opened to the atrium. II 11/8/2021   
Trash and Rubbish Disposal. (A) Only metal or UL- or FM-fire-resistant rated wastebaskets shall be used for trash. II 11/8/2021   
Oxygen storage shall be in accordance with NFPA 99, 1999 Edition. II/III 11/8/2021   
In facilities that are constructed or have plans approved after July 1, 2005, electrical wiring shall be installed and maintained in accordance with the requirements of the National Electrical Code, 1999 edition, National Fire Protection Association, Inc., incorporated by reference, in this rule and available by mail at One Batterymarch Park, Quincy, MA 02269, and local codes. This rule does not incorporate any subsequent amendments or additions to the materials incorporated by reference. Facilities built between September 28, 1979 and July 1, 2005 shall be maintained in accordance with the requirements of the National Electrical Code, which was in effect at the time of the original plan approval and local codes. This rule does not incorporate any subsequent amendments or additions. In facilities built prior to September 28, 1979, electrical wiring shall be maintained in good repair and shall not present a safety hazard. All facilities shall have wiring inspected every two (2) years by a qualified electrician. II/III 11/8/2021