Inspection Results
-
Facility failed to meet the following Requirement(s):Corrected DateLevel of HarmResidents Affected
Fire Drills and Emergency Preparedness. (A) All facilities shall have a written plan to meet potential emergencies or disasters and shall request consultation and assistance annually from a local fire unit for review of fire and evacuation plans. If the consultation cannot be obtained, the facility shall inform the state fire marshal in writing and request assistance in review of the plan. An up-to-date copy of the facility ' s entire plan shall be provided to the local jurisdiction ' s emergency management director. II/III   
Protection from Hazards. (I) In facilities whose plans were approved or which were initially licensed after December 31, 1987, for more than twenty (20) beds and all facilities licensed after August 28, 2007, each smoke section shall be separated by one- (1-) hour fire-rated smoke partitions. The smoke partitions shall be continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least twenty- (20-) minute fire-rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the complete fire alarm system. II