| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| Fire Drills and Emergency Preparedness.
(A) All facilities shall have a written plan to meet potential emergencies or disasters and shall request consultation and assistance annually from a local fire unit for review of fire and evacuation plans. If the consultation cannot be obtained, the facility shall inform the state fire marshal in writing and request assistance in review of the plan. An up-to-date copy of the facility ' s entire plan shall be provided to the local jurisdiction ' s emergency management director. II/III
|
1/9/2023
| | |
| Exits, Stairways, and Fire Escapes.
(E) If it is necessary to lock exit doors, the locks shall not require the use of a key, tool, special knowledge, or effort to unlock the door from inside the building. Only one (1) lock shall be permitted on each door. Delayed egress locks complying with section 7.2.1.6.1 of the 2000 edition NFPA 101 shall be permitted, provided that not more than one (1) such device is located in any egress path. Self-locking exit doors shall be equipped with a hold-open device to permit staff to reenter the building during the evacuation. I/II
|
1/9/2023
| | |
| Complete Fire Alarm Systems.
(B) Facilities that are required to install a sprinkler system in accordance with section (11) of this rule shall comply with the following requirements:
1. Until the required sprinkler system is installed, each resident room or any room designated for sleeping shall be equipped with at least one (1) battery-powered smoke alarm installed, tested, and maintained in accordance with manufacturer ' s specifications. In addition, the facility shall be equipped with interconnected heat detectors installed, tested, and maintained in accordance with NFPA 72, 1999 edition, with detectors in all areas subject to nuisance alarms, including, but not limited to, kitchens, laundries, bathrooms, mechanical air handling rooms, and attic spaces. I/II
A. The facility shall maintain a written record of the monthly testing and battery changes. The written records shall be retained for one (1) year. I/II
|
1/9/2023
| | |
| Complete Fire Alarm Systems.
(C) All facilities shall test and maintain the complete fire alarm system in accordance with NFPA 72, 1999 edition. I/II
|
1/9/2023
| | |
| Protection from Hazards.
(A) In assisted living facilities and residential care facilities licensed on or after November 13, 1980, for more than twelve (12) beds, hazardous areas shall be separated by construction of at least a one- (1-) hour fire-resistant rating. In facilities equipped with a complete fire alarm system, the one- (1-) hour fire separation is required only for furnace or boiler rooms. Hazardous areas equipped with a complete sprinkler system are not required to have this one- (1-) hour fire separation. Doors to hazardous areas shall be self-closing and shall be kept closed unless an electromagnetic hold-open device is used which is interconnected with the fire alarm system. When the sprinkler option is chosen, the areas shall be separated from other spaces by smoke-resistant partitions and doors. The doors shall be self-closing or automatic-closing. Facilities formerly licensed as residential care facility I or II, and existing prior to November 13, 1980, shall be exempt from this requirement. II
|
1/9/2023
| | |
| Protection from Hazards.
(H) All facilities shall be divided into at least two (2) smoke sections with each section not exceeding one hundred fifty feet (150') in length or width. If the floor ' s dimensions do not exceed seventy-five feet (75') in length or width, a division of the floor into two (2) smoke sections will not be required. II
|
1/9/2023
| | |
| Sprinkler Systems.
(B) Facilities that have a sprinkler system installed prior to August 28, 2007, shall inspect, maintain, and test these systems in accordance with the requirements that were in effect for such facilities on August 27, 2007. I/II
|
1/9/2023
| | |
| Emergency Lighting.
(C) If battery-powered lights are used, they shall be capable of operating the light for at least one and one-half (1 1/2) hours. II
|
1/9/2023
| | |
| Smoking.
(C) The contents of ashtrays shall be disposed of properly in receptacles made of noncombustible material. II/III
|
1/9/2023
| | |
| Oxygen storage shall be in accordance with NFPA 99, 1999 Edition. II/III
|
1/9/2023
| | |
| A reading light shall be provided for each resident desiring to read. Additional lighting shall be provided to meet the individual needs of each resident. III
|
1/9/2023
| | |
| The administrator shall be responsible for monitoring the health of the employees. II/III
|
1/9/2023
| | |
| The bond required by section 198.096, RSMo, for operators holding personal funds of residents shall be in a form approved by the department and shall provide that residents who allege that they have been wrongfully deprived of moneys held in trust may bring an action for recovery directly against the surety. The bond shall be in an amount equal to at least one and one-half (1 1/2) times the average monthly balance of the residents ' personal funds, including residents ' petty cash, or the average total of the monthly balances for the preceding twelve (12) months. The average monthly balance(s) or the average total of the monthly balance(s) shall be rounded to the nearest one thousand dollars ($1,000). One (1) bond may be used to cover the residents ' funds in more than one (1) facility operated by the same operator, if the facility is a multilicensed facility on the same premises. If not on the same premises, then one (1) bond may be used if the bond specifies the amount of coverage provided for each individual facility and the coverage for each facility is a minimum of one thousand dollars ($1,000). II/III
|
1/9/2023
| | |