| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| Fire Drills and Emergency Preparedness.
(A) All facilities shall have a written plan to meet potential emergencies or disasters and shall request consultation and assistance annually from a local fire unit for review of fire and evacuation plans. If the consultation cannot be obtained, the facility shall inform the state fire marshal in writing and request assistance in review of the plan. An up-to-date copy of the facility ' s entire plan shall be provided to the local jurisdiction ' s emergency management director. II/III
|
1/21/2025
| | |
| Fire Drills and Emergency Preparedness.
(D) A minimum of twelve (12) fire drills shall be conducted annually with at least one (1) every three (3) months on each shift. At least four (4) of the required fire drills must be unannounced to residents and staff, excluding staff who are assigned to evaluate staff and resident response to the fire drill. The fire drills shall include a resident evacuation at least once a year. II/III
|
1/21/2025
| | |
| Exit Signs.
(A) Signs bearing the word EXIT in plain, legible letters shall be placed at each required exit, except at doors directly from rooms to exit passageways or corridors. Letters of all exit signs shall be at least six inches (6") high and principle strokes three-fourths of an inch (3/4") wide, except that letters of internally illuminated exit signs shall not be less than four inches (4") high. II
|
1/21/2025
| | |
| Complete Fire Alarm Systems.
(B) Facilities that are required to install a sprinkler system in accordance with section (11) of this rule shall comply with the following requirements:
1. Until the required sprinkler system is installed, each resident room or any room designated for sleeping shall be equipped with at least one (1) battery-powered smoke alarm installed, tested, and maintained in accordance with manufacturer ' s specifications. In addition, the facility shall be equipped with interconnected heat detectors installed, tested, and maintained in accordance with NFPA 72, 1999 edition, with detectors in all areas subject to nuisance alarms, including, but not limited to, kitchens, laundries, bathrooms, mechanical air handling rooms, and attic spaces. I/II
A. The facility shall maintain a written record of the monthly testing and battery changes. The written records shall be retained for one (1) year. I/II
|
1/21/2025
| | |
| Complete Fire Alarm Systems.
(C) All facilities shall test and maintain the complete fire alarm system in accordance with NFPA 72, 1999 edition. I/II
|
1/21/2025
| | |
| Emergency Lighting.
(A) Emergency lighting of sufficient intensity shall be provided for exits, stairs, resident corridors, and required attendants ' station. II
|
1/21/2025
| | |
| Emergency Lighting.
(C) If battery-powered lights are used, they shall be capable of operating the light for at least one and one-half (1 1/2) hours. II
|
1/21/2025
| | |
| Interior Finish and Furnishings.
(D) All curtains and drapes in a licensed facility shall be certified or treated to be flame-resistant as defined in NFPA 101, 2000 edition. II
|
1/21/2025
| | |
| Trash and Rubbish Disposal.
(A) Only metal or UL- or FM-fire-resistant rated wastebaskets shall be used for trash. II
|
1/21/2025
| | |
| The building shall be substantially constructed and shall be maintained in good repair and in accordance with the construction and fire safety rules in effect at the time of initial licensing. II/III
|
1/21/2025
| | |
| All stairways shall be equipped with permanently secured handrails on at least one (1) side. III
|
1/21/2025
| | |
| In facilities that are constructed or have plans approved after July 1, 2005, electrical wiring shall be installed and maintained in accordance with the requirements of the National Electrical Code, 1999 edition, National Fire Protection Association, Inc., incorporated by reference, in this rule and available by mail at One Batterymarch Park, Quincy, MA 02269, and local codes. This rule does not incorporate any subsequent amendments or additions to the materials incorporated by reference. Facilities built between September 28, 1979 and July 1, 2005 shall be maintained in accordance with the requirements of the National Electrical Code, which was in effect at the time of the original plan approval and local codes. This rule does not incorporate any subsequent amendments or additions. In facilities built prior to September 28, 1979, electrical wiring shall be maintained in good repair and shall not present a safety hazard. All facilities shall have wiring inspected every two (2) years by a qualified electrician. II/III
|
1/21/2025
| | |