| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| Exit doors in newly licensed facilities shall be at least thirty-six inches (36") wide, at least seventy-two inches (72") high and shall swing outward. II/III
|
10/7/2025
| | |
| General Requirements.
(D) The department shall have the right of inspection of any portion of a building in which a licensed facility is located unless the unlicensed portion is separated by two- (2-) hour fire-resistant construction. No section of the building shall present a fire hazard. I/II
|
3/12/2026
| | |
| General Requirements.
(H) Facilities shall not use space under stairways to store combustible materials. I/II
|
7/31/2025
| | |
| Fire Extinguishers.
(D) All fire extinguishers shall bear the label of the Underwriters ' Laboratories (UL) or the Factory Mutual (FM) Laboratories and shall be installed and maintained in accordance with NFPA 10, 1998 edition. This includes the documentation and dating of a monthly pressure check. II/III
|
7/31/2025
| | |
| Exits, Stairways, and Fire Escapes.
(A) Each floor of a facility shall have at least two (2) unobstructed exits remote from each other. I/II
|
7/31/2025
| | |
| Exits, Stairways, and Fire Escapes.
(J) Fire escapes constructed on or after November 13, 1980, whether interior or exterior, shall be thirty-six inches (36") wide, shall have eight-inch (8") maximum risers, nine-inch (9") minimum tread, no winders, maximum height between landings of twelve feet (12'), minimum dimensions of landings of forty-four inches (44"), landings at each exit door, and handrails on both sides and be of sturdy construction, using at least two-inch (2") lumber. Exit doors to these fire escapes shall be at least thirty-six inches (36") wide and the door shall swing outward. II/III
|
12/10/2025
| | |
| Exit Signs.
(A) Signs bearing the word EXIT in plain, legible letters shall be placed at each required exit, except at doors directly from rooms to exit passageways or corridors. Letters of all exit signs shall be at least six inches (6") high and principle strokes three-fourths of an inch (3/4") wide, except that letters of internally illuminated exit signs shall not be less than four inches (4") high. II
|
10/7/2025
| | |
| Exit Signs.
(C) All required exit signs and directional indicators shall be positioned so that both normal and emergency lighting illuminates them. II/III
|
10/7/2025
| | |
| Complete Fire Alarm Systems.
(C) All facilities shall test and maintain the complete fire alarm system in accordance with NFPA 72, 1999 edition. I/II
|
7/31/2025
| | |
| Complete Fire Alarm Systems.
(D) All facilities shall have inspections and written certifications of the complete fire alarm system completed by an approved qualified service representative in accordance with NFPA 72, 1999 edition, at least annually. I/II
|
7/31/2025
| | |
| Protection from Hazards.
(A) In assisted living facilities and residential care facilities licensed on or after November 13, 1980, for more than twelve (12) beds, hazardous areas shall be separated by construction of at least a one- (1-) hour fire-resistant rating. In facilities equipped with a complete fire alarm system, the one- (1-) hour fire separation is required only for furnace or boiler rooms. Hazardous areas equipped with a complete sprinkler system are not required to have this one- (1-) hour fire separation. Doors to hazardous areas shall be self-closing and shall be kept closed unless an electromagnetic hold-open device is used which is interconnected with the fire alarm system. When the sprinkler option is chosen, the areas shall be separated from other spaces by smoke-resistant partitions and doors. The doors shall be self-closing or automatic-closing. Facilities formerly licensed as residential care facility I or II, and existing prior to November 13, 1980, shall be exempt from this requirement. II
|
3/12/2026
| | |
| Protection from Hazards.
(B) The storage of unnecessary combustible materials in any part of a building in which a licensed facility is located is prohibited. I/II
|
3/12/2026
| | |
| Protection from Hazards.
(L) If two (2) or more levels of long-term care or two (2) different businesses are located in the same building, the entire building shall meet either the most strict construction and fire safety standards for the combined facility or the facilities shall be separated from the other(s) by two- (2-) hour fire-resistant construction. In buildings equipped with a complete sprinkler system in accordance with NFPA 13 or NFPA 13R, 1999 edition, this separation may be rated at one (1) hour. II
|
7/31/2025
| | |
| Emergency Lighting.
(A) Emergency lighting of sufficient intensity shall be provided for exits, stairs, resident corridors, and required attendants ' station. II
|
7/31/2025
| | |
| Emergency Lighting.
(C) If battery-powered lights are used, they shall be capable of operating the light for at least one and one-half (1 1/2) hours. II
|
7/31/2025
| | |
| Interior Finish and Furnishings.
(A) In a facility licensed on or after November 13, 1980, for more than twelve (12) beds, wall and ceiling surfaces of all occupied rooms and all exitways shall be classified either Class A or B interior finish as defined in NFPA 101, 2000 edition. II
|
3/12/2026
| | |
| Interior Finish and Furnishings.
(C) In facilities licensed for more than twelve (12) beds, the new or replacement floor covering and carpeting in buildings that do not have a sprinkler system shall be Class I in accordance with NFPA 253, 2000 edition. II/III
|
7/31/2025
| | |
| Interior Finish and Furnishings.
(D) All curtains and drapes in a licensed facility shall be certified or treated to be flame-resistant as defined in NFPA 101, 2000 edition. II
|
7/31/2025
| | |
| The building shall be substantially constructed and shall be maintained in good repair and in accordance with the construction and fire safety rules in effect at the time of initial licensing. II/III
|
5/5/2026
| | |
| In facilities that are constructed or have plans approved after July 1, 2005, electrical wiring shall be installed and maintained in accordance with the requirements of the National Electrical Code, 1999 edition, National Fire Protection Association, Inc., incorporated by reference, in this rule and available by mail at One Batterymarch Park, Quincy, MA 02269, and local codes. This rule does not incorporate any subsequent amendments or additions to the materials incorporated by reference. Facilities built between September 28, 1979 and July 1, 2005 shall be maintained in accordance with the requirements of the National Electrical Code, which was in effect at the time of the original plan approval and local codes. This rule does not incorporate any subsequent amendments or additions. In facilities built prior to September 28, 1979, electrical wiring shall be maintained in good repair and shall not present a safety hazard. All facilities shall have wiring inspected every two (2) years by a qualified electrician. II/III
|
10/7/2025
| | |
| If extension cords are used, they must be Underwriters ' Laboratory (UL)-approved or shall comply with other recognized electrical appliance approval standards and sized to carry the current required for the appliance used. Only one (1) appliance shall be connected to one (1) extension cord and only two (2) appliances may be served by one (1) duplex receptacle. If extension cords are used, they shall not be placed under rugs, through doorways or located where they are subject to physical damage. II/III
|
7/31/2025
| | |
| Each window shall be provided with a shade, drape or curtain to restrict the amount of sunlight when necessary. III
|
7/31/2025
| | |