| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| Fire Drills and Emergency Preparedness.
(F) The fire alarm shall be activated during all fire drills unless the drill is conducted between 9 p.m. and 6 a.m., when a facility-generated predetermined message is acceptable in lieu of the audible and visual components of the fire alarm. II/III
|
| | |
| Fire Safety Training Requirements.
(A) The facility shall ensure that fire safety training is provided to all employees:
1. During employee orientation;
2. At least every six (6) months; and
3. When training needs are identified as a result of fire drill evaluations. II/III
|
| | |
| Exits, Stairways, and Fire Escapes.
(E) If it is necessary to lock exit doors, the locks shall not require the use of a key, tool, special knowledge, or effort to unlock the door from inside the building. Only one (1) lock shall be permitted on each door. Delayed egress locks complying with section 7.2.1.6.1 of the 2000 edition NFPA 101 shall be permitted, provided that not more than one (1) such device is located in any egress path. Self-locking exit doors shall be equipped with a hold-open device to permit staff to reenter the building during the evacuation. I/II
|
| | |
| Complete Fire Alarm Systems.
(A) All facilities shall have a complete fire alarm system installed in accordance with NFPA 101, Section 18.3.4, 2000 edition. The complete fire alarm shall automatically transmit to the fire department, dispatching agency, or central monitoring company. The complete fire alarm system shall include visual signals and audible alarms that can be heard throughout the building and a main panel that interconnects all alarm-activating devices and audible signals. Manual pull stations shall be installed at or near each required attendant ' s station and each required exit. I/II
|
| | |
| Protection from Hazards.
(G) All doors providing separation between floors shall have a self-closing device attached. If the doors are to be held open, electromagnetic hold-open devices shall be used that are interconnected with either an individual smoke detector or a complete fire alarm system. II
|
| | |
| Protection from Hazards.
(J) In all facilities that were initially licensed on or prior to December 31, 1987, and all facilities licensed for twenty (20) or fewer beds prior to August 28, 2007, each smoke section shall be separated by a one- (1-) hour fire-rated smoke partition that extends from the inside portion of an exterior wall to the inside portion of an exterior wall and from the floor to the underside of the floor or roof deck above, through any concealed spaces, such as those above suspended ceilings, and through interstitial structural and mechanical spaces. Smoke partitions shall be permitted to terminate at the underside of a monolithic or suspending ceiling system where the following conditions are met: The ceiling system forms a continuous membrane, a smoketight joint is provided between the top of the smoke partition and the bottom of the suspended ceiling and the space above the ceiling is not used as a plenum. Smoke partition doors shall be at least twenty- (20-) minute fire-rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the complete fire alarm system. II
|
| | |
| If elevators are used, installation and maintenance shall comply with local and state codes and the National Electric Code. II/III
|
| | |
| Plumbing fixtures which are accessible to residents and which supply hot water shall be thermostatically controlled so that the water temperature at the fixture does not exceed one hundred twenty degrees Fahrenheit (120��F) (49��C) and the water shall be at a temperature range between one hundred five degrees Fahrenheit (105��F) (41��C) and one hundred twenty degrees Fahrenheit (120��F) (49��C). I/II
|
| | |