| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| Range Hood Extinguishing Systems.
(C) The range hood and its extinguishing system shall be certified at least twice annually in accordance with NFPA 96, 1998 edition. II/III
|
4/16/2025
| | |
| Exits, Stairways, and Fire Escapes.
(E) If it is necessary to lock exit doors, the locks shall not require the use of a key, tool, special knowledge, or effort to unlock the door from inside the building. Only one (1) lock shall be permitted on each door. Delayed egress locks complying with section 7.2.1.6.1 of the 2000 edition NFPA 101 shall be permitted, provided that not more than one (1) such device is located in any egress path. Self-locking exit doors shall be equipped with a hold-open device to permit staff to reenter the building during the evacuation. I/II
|
4/16/2025
| | |
| Exits, Stairways, and Fire Escapes.
(G) All stairways and corridors shall be easily negotiable and shall be maintained free of obstructions. II
|
4/16/2025
| | |
| Emergency Lighting.
(C) If battery-powered lights are used, they shall be capable of operating the light for at least one and one-half (1 1/2) hours. II
|
4/16/2025
| | |