Facility failed to meet the following Requirement(s):Corrected DateLevel of HarmResidents Affected
General Requirements. (D) The department shall have the right of inspection of any portion of a building in which a licensed facility is located unless the unlicensed portion is separated by two- (2-) hour fire-resistant construction. No section of the building shall present a fire hazard. I/II 5/18/2022   
Fire Extinguishers. (D) All fire extinguishers shall bear the label of the Underwriters ' Laboratories (UL) or the Factory Mutual (FM) Laboratories and shall be installed and maintained in accordance with NFPA 10, 1998 edition. This includes the documentation and dating of a monthly pressure check. II/III 5/18/2022   
Fire Drills and Emergency Preparedness. (D) A minimum of twelve (12) fire drills shall be conducted annually with at least one (1) every three (3) months on each shift. At least four (4) of the required fire drills must be unannounced to residents and staff, excluding staff who are assigned to evaluate staff and resident response to the fire drill. The fire drills shall include a resident evacuation at least once a year. II/III 5/18/2022   
Sprinkler Systems. (A) Facilities licensed on or after August 28, 2007, or any section of a facility in which a major renovation has been completed on or after August 28, 2007, shall install and maintain a complete sprinkler system in accordance with NFPA 13, 1999 edition. I/II 5/18/2022   
Trash and Rubbish Disposal. (A) Only metal or UL- or FM-fire-resistant rated wastebaskets shall be used for trash. II 5/18/2022   
The building shall be substantially constructed and shall be maintained in good repair and in accordance with the construction and fire safety rules in effect at the time of initial licensing. II/III 5/18/2022   
Lighting is restricted to electricity. II