Inspection Results
-
Facility failed to meet the following Requirement(s):Corrected DateLevel of HarmResidents Affected
Fire Drills and Emergency Preparedness. (B) The plan shall include, but is not limited to, the following: 1. A phased response ranging from relocation of residents to an immediate area within the facility; relocation to an area of refuge, if applicable; or to total building evacuation. This phased response part of the plan shall be consistent with the direction of the local fire unit or state fire marshal and appropriate for the fire or emergency; 2. Written instructions for evacuation of each floor including evacuation to areas of refuge, if applicable, and a floor plan showing the location of exits, fire alarm pull stations, fire extinguishers, and any areas of refuge; 3. Evacuating residents, if necessary, from an area of refuge to a point of safety outside the building; 4. The location of any additional water sources on the property such as cisterns, wells, lagoons, ponds, or creeks; 5. Procedures for the safety and comfort of residents evacuated; 6. Staffing assignments; 7. Instructions for staff to call the fire department or other outside emergency services; 8. Instructions for staff to call alternative resource(s) for housing residents, if necessary; 9. Administrative staff responsibilities; and 10. Designation of a staff member to be responsible for accounting for all residents ' whereabouts. II/III 11/19/2019   
Plumbing fixtures which are accessible to residents and which supply hot water shall be thermostatically controlled so that the water temperature at the fixture does not exceed one hundred twenty degrees Fahrenheit (120?F) (49?C) and the water shall be at a temperature range between one hundred five degrees Fahrenheit (105?F) (41?C) and one hundred twenty degrees Fahrenheit (120?F) (49?C). I/II 11/19/2019   
The potable water system shall be installed to preclude the possibility of backflow. Devices shall be installed to protect against backflow and back siphonage at all fixtures and equipment where an air gap at least twice the diameter of the water supply inlet is not provided between the water supply inlet and the fixture ' s flood level rim. A hose shall not be attached to a faucet unless a backflow prevention device is installed. II 11/19/2019