Inspection Results
-
Facility failed to meet the following Requirement(s):Corrected DateLevel of HarmResidents Affected
Fire Extinguishers. (D) All fire extinguishers shall bear the label of the Underwriters ' Laboratories (UL) or the Factory Mutual (FM) Laboratories and shall be installed and maintained in accordance with NFPA 10, 1998 edition. This includes the documentation and dating of a monthly pressure check. II/III   
Fire Drills and Emergency Preparedness. (D) A minimum of twelve (12) fire drills shall be conducted annually with at least one (1) every three (3) months on each shift. At least four (4) of the required fire drills must be unannounced to residents and staff, excluding staff who are assigned to evaluate staff and resident response to the fire drill. The fire drills shall include a resident evacuation at least once a year. II/III   
Complete Fire Alarm Systems. (C) All facilities shall test and maintain the complete fire alarm system in accordance with NFPA 72, 1999 edition. I/II   
Complete Fire Alarm Systems. (E) Facilities shall test by activating the complete fire alarm system at least once a month. I/II   
Interior Finish and Furnishings. (D) All curtains and drapes in a licensed facility shall be certified or treated to be flame-resistant as defined in NFPA 101, 2000 edition. II