| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| Range Hood Extinguishing Systems.
(C) The range hood and its extinguishing system shall be certified at least twice annually in accordance with NFPA 96, 1998 edition. II/III
|
12/23/2019
| | |
| Fire Drills and Emergency Preparedness.
(D) A minimum of twelve (12) fire drills shall be conducted annually with at least one (1) every three (3) months on each shift. At least four (4) of the required fire drills must be unannounced to residents and staff, excluding staff who are assigned to evaluate staff and resident response to the fire drill. The fire drills shall include a resident evacuation at least once a year. II/III
|
10/1/2019
| | |
| Fire Safety Training Requirements.
(A) The facility shall ensure that fire safety training is provided to all employees:
1. During employee orientation;
2. At least every six (6) months; and
3. When training needs are identified as a result of fire drill evaluations. II/III
|
10/1/2019
| | |
| Protection from Hazards.
(A) In assisted living facilities and residential care facilities licensed on or after November 13, 1980, for more than twelve (12) beds, hazardous areas shall be separated by construction of at least a one- (1-) hour fire-resistant rating. In facilities equipped with a complete fire alarm system, the one- (1-) hour fire separation is required only for furnace or boiler rooms. Hazardous areas equipped with a complete sprinkler system are not required to have this one- (1-) hour fire separation. Doors to hazardous areas shall be self-closing and shall be kept closed unless an electromagnetic hold-open device is used which is interconnected with the fire alarm system. When the sprinkler option is chosen, the areas shall be separated from other spaces by smoke-resistant partitions and doors. The doors shall be self-closing or automatic-closing. Facilities formerly licensed as residential care facility I or II, and existing prior to November 13, 1980, shall be exempt from this requirement. II
|
10/1/2019
| | |
| Sprinkler Systems.
(A) Facilities licensed on or after August 28, 2007, or any section of a facility in which a major renovation has been completed on or after August 28, 2007, shall install and maintain a complete sprinkler system in accordance with NFPA 13, 1999 edition. I/II
|
10/1/2019
| | |
| Emergency Lighting.
(C) If battery-powered lights are used, they shall be capable of operating the light for at least one and one-half (1 1/2) hours. II
|
10/1/2019
| | |
| In newly licensed facilities or if a new heating system is installed in an existing licensed facility, the heating of the building shall be restricted to steam, hot water, permanently installed electric heating devices or a warm air system employing central heating plants with installation such as to safeguard the inherent fire hazard, or approved installation of outside wall heaters which bear the approved label of the American Gas Association or National Board of Fire Underwriters. The foregoing requirements are applicable to residential care facilities. In assisted living facilities, the heating of the building shall be restricted to steam, hot water, permanently installed electric heating devices or a warm air system employing central heating plants with installation such as to safeguard the inherent fire hazard, or approved installation of outside wall heaters which bear the approved label of the American Gas Association or National Board of Fire Underwriters. For all facilities, oil or gas heating appliances shall be properly vented to the outside and the use of portable heaters of any kind is prohibited. If approved wall heaters are used, adequate guards shall be provided to safeguard residents. I/II
|
10/1/2019
| | |
| In facilities that are constructed or have plans approved after July 1, 2005, electrical wiring shall be installed and maintained in accordance with the requirements of the National Electrical Code, 1999 edition, National Fire Protection Association, Inc., incorporated by reference, in this rule and available by mail at One Batterymarch Park, Quincy, MA 02269, and local codes. This rule does not incorporate any subsequent amendments or additions to the materials incorporated by reference. Facilities built between September 28, 1979 and July 1, 2005 shall be maintained in accordance with the requirements of the National Electrical Code, which was in effect at the time of the original plan approval and local codes. This rule does not incorporate any subsequent amendments or additions. In facilities built prior to September 28, 1979, electrical wiring shall be maintained in good repair and shall not present a safety hazard. All facilities shall have wiring inspected every two (2) years by a qualified electrician. II/III
|
10/1/2019
| | |