| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| Fire Safety Training Requirements.
(A) The facility shall ensure that fire safety training is provided to all employees:
1. During employee orientation;
2. At least every six (6) months; and
3. When training needs are identified as a result of fire drill evaluations. II/III
|
1/6/2023
| | |
| Complete Fire Alarm Systems.
(C) All facilities shall test and maintain the complete fire alarm system in accordance with NFPA 72, 1999 edition. I/II
|
12/5/2022
| | |
| Protection from Hazards.
(A) In assisted living facilities and residential care facilities licensed on or after November 13, 1980, for more than twelve (12) beds, hazardous areas shall be separated by construction of at least a one- (1-) hour fire-resistant rating. In facilities equipped with a complete fire alarm system, the one- (1-) hour fire separation is required only for furnace or boiler rooms. Hazardous areas equipped with a complete sprinkler system are not required to have this one- (1-) hour fire separation. Doors to hazardous areas shall be self-closing and shall be kept closed unless an electromagnetic hold-open device is used which is interconnected with the fire alarm system. When the sprinkler option is chosen, the areas shall be separated from other spaces by smoke-resistant partitions and doors. The doors shall be self-closing or automatic-closing. Facilities formerly licensed as residential care facility I or II, and existing prior to November 13, 1980, shall be exempt from this requirement. II
|
12/15/2022
| | |
| Sprinkler Systems.
(F) All facilities shall have inspections and written certifications of the approved sprinkler system completed by an approved qualified service representative in accordance with NFPA 25, 1998 edition. The inspections shall be in accordance with the provisions of NFPA 25, 1998 edition, with certification at least annually by a qualified service representative. I/II
|
1/10/2023
| | |
| Emergency Lighting.
(C) If battery-powered lights are used, they shall be capable of operating the light for at least one and one-half (1 1/2) hours. II
|
1/6/2023
| | |
| The building shall be substantially constructed and shall be maintained in good repair and in accordance with the construction and fire safety rules in effect at the time of initial licensing. II/III
|
1/13/2023
| | |
| In facilities that are constructed or have plans approved after July 1, 2005, electrical wiring shall be installed and maintained in accordance with the requirements of the National Electrical Code, 1999 edition, National Fire Protection Association, Inc., incorporated by reference, in this rule and available by mail at One Batterymarch Park, Quincy, MA 02269, and local codes. This rule does not incorporate any subsequent amendments or additions to the materials incorporated by reference. Facilities built between September 28, 1979 and July 1, 2005 shall be maintained in accordance with the requirements of the National Electrical Code, which was in effect at the time of the original plan approval and local codes. This rule does not incorporate any subsequent amendments or additions. In facilities built prior to September 28, 1979, electrical wiring shall be maintained in good repair and shall not present a safety hazard. All facilities shall have wiring inspected every two (2) years by a qualified electrician. II/III
|
12/19/2022
| | |
| Employees shall thoroughly wash their hands and the exposed portions of their arms with soap and warm water before starting work, during work as often as is necessary to keep them clean and after smoking, eating, drinking or using the toilet. Employees shall keep their fingernails clean and trimmed. II/III
|
1/6/2023
| | |