Inspection Results
-
Facility failed to meet the following Requirement(s):Corrected DateLevel of HarmResidents Affected
General Requirements. (D) The department shall have the right of inspection of any portion of a building in which a licensed facility is located unless the unlicensed portion is separated by two- (2-) hour fire-resistant construction. No section of the building shall present a fire hazard. I/II 2/28/2024   
Fire Extinguishers. (D) All fire extinguishers shall bear the label of the Underwriters ' Laboratories (UL) or the Factory Mutual (FM) Laboratories and shall be installed and maintained in accordance with NFPA 10, 1998 edition. This includes the documentation and dating of a monthly pressure check. II/III 2/28/2024   
Complete Fire Alarm Systems. (C) All facilities shall test and maintain the complete fire alarm system in accordance with NFPA 72, 1999 edition. I/II 4/10/2024   
Complete Fire Alarm Systems. (D) All facilities shall have inspections and written certifications of the complete fire alarm system completed by an approved qualified service representative in accordance with NFPA 72, 1999 edition, at least annually. I/II 2/28/2024   
Protection from Hazards. (A) In assisted living facilities and residential care facilities licensed on or after November 13, 1980, for more than twelve (12) beds, hazardous areas shall be separated by construction of at least a one- (1-) hour fire-resistant rating. In facilities equipped with a complete fire alarm system, the one- (1-) hour fire separation is required only for furnace or boiler rooms. Hazardous areas equipped with a complete sprinkler system are not required to have this one- (1-) hour fire separation. Doors to hazardous areas shall be self-closing and shall be kept closed unless an electromagnetic hold-open device is used which is interconnected with the fire alarm system. When the sprinkler option is chosen, the areas shall be separated from other spaces by smoke-resistant partitions and doors. The doors shall be self-closing or automatic-closing. Facilities formerly licensed as residential care facility I or II, and existing prior to November 13, 1980, shall be exempt from this requirement. II 2/28/2024   
Emergency Lighting. (C) If battery-powered lights are used, they shall be capable of operating the light for at least one and one-half (1 1/2) hours. II 4/10/2024