| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| |
| | |
| |
| | |
| Emergency Lighting
Emergency lighting of at least 1-1/2 hour duration is provided automatically in accordance with 7.9.
18.2.9.1, 19.2.9.1 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Emergency Lighting
Emergency lighting of at least 1-1/2 hour duration is provided automatically in accordance with 7.9.
18.2.9.1, 19.2.9.1 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Emergency Lighting
Emergency lighting of at least 1-1/2 hour duration is provided automatically in accordance with 7.9.
18.2.9.1, 19.2.9.1 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Emergency Lighting
Emergency lighting of at least 1-1/2 hour duration is provided automatically in accordance with 7.9.
18.2.9.1, 19.2.9.1 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Emergency Lighting
Emergency lighting of at least 1-1/2 hour duration is provided automatically in accordance with 7.9.
18.2.9.1, 19.2.9.1 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Emergency Lighting
Emergency lighting of at least 1-1/2 hour duration is provided automatically in accordance with 7.9.
18.2.9.1, 19.2.9.1 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Emergency Lighting
Emergency lighting of at least 1-1/2 hour duration is provided automatically in accordance with 7.9.
18.2.9.1, 19.2.9.1 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Emergency Lighting
Emergency lighting of at least 1-1/2 hour duration is provided automatically in accordance with 7.9.
18.2.9.1, 19.2.9.1 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 NEW
Smoke barriers shall be constructed to provide at least a one hour fire resistance rating and constructed in accordance with 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations of fully ducted HVAC systems.
18.3.7.3, 18.3.7.4, 18.3.7.5, 8.3
Describe any mechanical smoke control system in REMARKS. |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 NEW
Smoke barriers shall be constructed to provide at least a one hour fire resistance rating and constructed in accordance with 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations of fully ducted HVAC systems.
18.3.7.3, 18.3.7.4, 18.3.7.5, 8.3
Describe any mechanical smoke control system in REMARKS. |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 NEW
Smoke barriers shall be constructed to provide at least a one hour fire resistance rating and constructed in accordance with 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations of fully ducted HVAC systems.
18.3.7.3, 18.3.7.4, 18.3.7.5, 8.3
Describe any mechanical smoke control system in REMARKS. |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 NEW
Smoke barriers shall be constructed to provide at least a one hour fire resistance rating and constructed in accordance with 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations of fully ducted HVAC systems.
18.3.7.3, 18.3.7.4, 18.3.7.5, 8.3
Describe any mechanical smoke control system in REMARKS. |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 NEW
Smoke barriers shall be constructed to provide at least a one hour fire resistance rating and constructed in accordance with 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations of fully ducted HVAC systems.
18.3.7.3, 18.3.7.4, 18.3.7.5, 8.3
Describe any mechanical smoke control system in REMARKS. |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 NEW
Smoke barriers shall be constructed to provide at least a one hour fire resistance rating and constructed in accordance with 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations of fully ducted HVAC systems.
18.3.7.3, 18.3.7.4, 18.3.7.5, 8.3
Describe any mechanical smoke control system in REMARKS. |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 NEW
Smoke barriers shall be constructed to provide at least a one hour fire resistance rating and constructed in accordance with 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations of fully ducted HVAC systems.
18.3.7.3, 18.3.7.4, 18.3.7.5, 8.3
Describe any mechanical smoke control system in REMARKS. |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Subdivision of Building Spaces - Smoke Barrier Construction
2012 NEW
Smoke barriers shall be constructed to provide at least a one hour fire resistance rating and constructed in accordance with 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations of fully ducted HVAC systems.
18.3.7.3, 18.3.7.4, 18.3.7.5, 8.3
Describe any mechanical smoke control system in REMARKS. |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
18.7.1.4 through 18.7.1.7 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
18.7.1.4 through 18.7.1.7 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
18.7.1.4 through 18.7.1.7 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
18.7.1.4 through 18.7.1.7 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
18.7.1.4 through 18.7.1.7 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
18.7.1.4 through 18.7.1.7 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
18.7.1.4 through 18.7.1.7 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
18.7.1.4 through 18.7.1.7 |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Maintenance, Inspection & Testing - Doors
Fire doors assemblies are inspected and tested annually in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives.
Non-rated doors, including corridor doors to patient rooms and smoke barrier doors, are routinely inspected as part of the facility maintenance program.
Individuals performing the door inspections and testing possess knowledge, training or experience that demonstrates ability.
Written records of inspection and testing are maintained and are available for review.
18.7.6, 8.3.3.1 (LSC)
5.2, 5.2.3 (NFPA 80) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Maintenance, Inspection & Testing - Doors
Fire doors assemblies are inspected and tested annually in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives.
Non-rated doors, including corridor doors to patient rooms and smoke barrier doors, are routinely inspected as part of the facility maintenance program.
Individuals performing the door inspections and testing possess knowledge, training or experience that demonstrates ability.
Written records of inspection and testing are maintained and are available for review.
18.7.6, 8.3.3.1 (LSC)
5.2, 5.2.3 (NFPA 80) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Maintenance, Inspection & Testing - Doors
Fire doors assemblies are inspected and tested annually in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives.
Non-rated doors, including corridor doors to patient rooms and smoke barrier doors, are routinely inspected as part of the facility maintenance program.
Individuals performing the door inspections and testing possess knowledge, training or experience that demonstrates ability.
Written records of inspection and testing are maintained and are available for review.
18.7.6, 8.3.3.1 (LSC)
5.2, 5.2.3 (NFPA 80) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Maintenance, Inspection & Testing - Doors
Fire doors assemblies are inspected and tested annually in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives.
Non-rated doors, including corridor doors to patient rooms and smoke barrier doors, are routinely inspected as part of the facility maintenance program.
Individuals performing the door inspections and testing possess knowledge, training or experience that demonstrates ability.
Written records of inspection and testing are maintained and are available for review.
18.7.6, 8.3.3.1 (LSC)
5.2, 5.2.3 (NFPA 80) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Maintenance, Inspection & Testing - Doors
Fire doors assemblies are inspected and tested annually in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives.
Non-rated doors, including corridor doors to patient rooms and smoke barrier doors, are routinely inspected as part of the facility maintenance program.
Individuals performing the door inspections and testing possess knowledge, training or experience that demonstrates ability.
Written records of inspection and testing are maintained and are available for review.
18.7.6, 8.3.3.1 (LSC)
5.2, 5.2.3 (NFPA 80) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Maintenance, Inspection & Testing - Doors
Fire doors assemblies are inspected and tested annually in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives.
Non-rated doors, including corridor doors to patient rooms and smoke barrier doors, are routinely inspected as part of the facility maintenance program.
Individuals performing the door inspections and testing possess knowledge, training or experience that demonstrates ability.
Written records of inspection and testing are maintained and are available for review.
18.7.6, 8.3.3.1 (LSC)
5.2, 5.2.3 (NFPA 80) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Maintenance, Inspection & Testing - Doors
Fire doors assemblies are inspected and tested annually in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives.
Non-rated doors, including corridor doors to patient rooms and smoke barrier doors, are routinely inspected as part of the facility maintenance program.
Individuals performing the door inspections and testing possess knowledge, training or experience that demonstrates ability.
Written records of inspection and testing are maintained and are available for review.
18.7.6, 8.3.3.1 (LSC)
5.2, 5.2.3 (NFPA 80) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Maintenance, Inspection & Testing - Doors
Fire doors assemblies are inspected and tested annually in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives.
Non-rated doors, including corridor doors to patient rooms and smoke barrier doors, are routinely inspected as part of the facility maintenance program.
Individuals performing the door inspections and testing possess knowledge, training or experience that demonstrates ability.
Written records of inspection and testing are maintained and are available for review.
18.7.6, 8.3.3.1 (LSC)
5.2, 5.2.3 (NFPA 80) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70) |
8/12/2022
| No actual Harm with potential for More than minimal harm that is not immediate jeopardy | Many |
| Complete Fire Alarm Systems.
(F) Facilities shall maintain a record of the complete fire alarm system tests, inspections and certifications required by subsections (10)(B), (10)(C), and (10)(E) of this rule. III
|
8/12/2022
| | |
| Sprinkler System.
(C) Facilities that have a sprinkler system installed prior to August 28, 2007, shall inspect, maintain, and test these systems in accordance with the requirements in effect for such facilities on August 27, 2007. I/II
|
8/12/2022
| | |
| Facilities shall have emergency lighting of sufficient intensity to provide for the safety of residents and other people using any exit, stairway, and corridor. The lighting shall be supplied by an emergency service, an automatic emergency generator or battery lighting system. This emergency lighting system shall be equipped with an automatic transfer switch. In an existing licensed facility, battery lights, if used, shall be wet cell units or other rechargeable-type batteries that shall be UL-approved and capable of operating the light for at least one and one-half (1½) hours. Battery-operated emergency lighting shall be tested for at least thirty (30) seconds every thirty (30) days, and an annual function test shall be conducted for the full operational duration of one and one-half (1½) hours. Records of these tests shall be documented and maintained for review. II
|
8/12/2022
| | |
| Each smoke section shall be separated by one- (1-) hour fire-rated walls that are continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least twenty- (20-) minute fire rated or its equivalent, self-closing, and may be held open only if the door closes automatically upon activation of the fire alarm system. II
|
8/12/2022
| | |
| (D) A minimum of twelve (12) fire drills shall be conducted annually with at least one (1) every three (3) months on each shift. At least four (4) of the required fire drills must be unannounced to residents and staff, excluding staff who are assigned to evaluate staff and resident response to the fire drill. The fire drills shall include a simulated resident evacuation that involves the local fire department or emergency service at least once a year. II/III
|
8/12/2022
| | |
| Electrical Wiring Requirements.
(A) Electrical wiring and equipment shall be installed and maintained in accordance with the NFPA 70, 1999 edition. Facilities that were complying prior to the effective date of this rule with prior editions of the NFPA 70 referenced in this rule shall be permitted to continue to comply with the earlier editions, as long as there is not an imminent danger to the health, safety, or welfare of any resident or a substantial probability that death or serious physical harm would result as determined by the department. II/III
|
8/12/2022
| | |