Inspection Results
-
Facility failed to meet the following Requirement(s):Corrected DateLevel of HarmResidents Affected
General Requirements. (D) The department shall have the right of inspection of any portion of a building in which a licensed facility is located unless the unlicensed portion is separated by two- (2-) hour fire-resistant construction. No section of the building shall present a fire hazard. I/II 2/22/2025   
Fire Extinguishers. (D) All fire extinguishers shall bear the label of the Underwriters ' Laboratories (UL) or the Factory Mutual (FM) Laboratories and shall be installed and maintained in accordance with NFPA 10, 1998 edition. This includes the documentation and dating of a monthly pressure check. II/III 2/22/2025   
Fire Drills and Emergency Preparedness. (B) The plan shall include, but is not limited to, the following: 1. A phased response ranging from relocation of residents to an immediate area within the facility; relocation to an area of refuge, if applicable; or to total building evacuation. This phased response part of the plan shall be consistent with the direction of the local fire unit or state fire marshal and appropriate for the fire or emergency; 2. Written instructions for evacuation of each floor including evacuation to areas of refuge, if applicable, and a floor plan showing the location of exits, fire alarm pull stations, fire extinguishers, and any areas of refuge; 3. Evacuating residents, if necessary, from an area of refuge to a point of safety outside the building; 4. The location of any additional water sources on the property such as cisterns, wells, lagoons, ponds, or creeks; 5. Procedures for the safety and comfort of residents evacuated; 6. Staffing assignments; 7. Instructions for staff to call the fire department or other outside emergency services; 8. Instructions for staff to call alternative resource(s) for housing residents, if necessary; 9. Administrative staff responsibilities; and 10. Designation of a staff member to be responsible for accounting for all residents ' whereabouts. II/III 2/22/2025   
Exits, Stairways, and Fire Escapes. (A) Each floor of a facility shall have at least two (2) unobstructed exits remote from each other. I/II 2/22/2025   
Exit Signs. (A) Signs bearing the word EXIT in plain, legible letters shall be placed at each required exit, except at doors directly from rooms to exit passageways or corridors. Letters of all exit signs shall be at least six inches (6") high and principle strokes three-fourths of an inch (3/4") wide, except that letters of internally illuminated exit signs shall not be less than four inches (4") high. II 2/22/2025   
Exit Signs. (B) Directional indicators showing the direction of travel shall be placed in corridors, passageways, or other locations where the direction of travel to reach the nearest exit is not apparent. II/III 8/5/2025   
Protection from Hazards. (B) The storage of unnecessary combustible materials in any part of a building in which a licensed facility is located is prohibited. I/II 2/22/2025   
Smoking. (B) Ashtrays shall be made of noncombustible material and safe design and shall be provided in all areas where smoking is permitted. II/III 2/22/2025   
Oxygen storage shall be in accordance with NFPA 99, 1999 Edition. II/III 2/22/2025   
The building shall be substantially constructed and shall be maintained in good repair and in accordance with the construction and fire safety rules in effect at the time of initial licensing. II/III   
In facilities that are constructed or have plans approved after July 1, 2005, electrical wiring shall be installed and maintained in accordance with the requirements of the National Electrical Code, 1999 edition, National Fire Protection Association, Inc., incorporated by reference, in this rule and available by mail at One Batterymarch Park, Quincy, MA 02269, and local codes. This rule does not incorporate any subsequent amendments or additions to the materials incorporated by reference. Facilities built between September 28, 1979 and July 1, 2005 shall be maintained in accordance with the requirements of the National Electrical Code, which was in effect at the time of the original plan approval and local codes. This rule does not incorporate any subsequent amendments or additions. In facilities built prior to September 28, 1979, electrical wiring shall be maintained in good repair and shall not present a safety hazard. All facilities shall have wiring inspected every two (2) years by a qualified electrician. II/III 2/22/2025   
A reading light shall be provided for each resident desiring to read. Additional lighting shall be provided to meet the individual needs of each resident. III 2/22/2025   
Effective measures intended to minimize the presence of rodents, flies, cockroaches and other insects on the premises shall be utilized. The premises shall be kept in such condition as to prevent the harborage or feeding of insects or rodents. II/III 2/22/2025   
At all times, including while being stored, prepared, displayed, served or transported to or from the facility, food shall be protected from potential contamination, including dust, insects, rodents, unclean equipment and utensils, unnecessary handling, coughs and sneezes, flooding, drainage and overhead leakage or overhead drippage from condensation. The temperature of potentially hazardous food shall be forty-five degrees Fahrenheit (45��F) or below or one hundred forty degrees Fahrenheit (140��F) or above at all times, except as otherwise provided in this section. In the event of a fire, flood, power outage or similar event that might result in the contamination of food, or that might prevent potentially hazardous food from being held at required temperatures, the person in charge shall immediately contact the Department of Health and Senior Services (the department). Upon receiving notice of this occurrence, the department shall take whatever action that it deems necessary to protect the residents. II/III 2/22/2025