| Facility failed to meet the following Requirement(s): | Corrected Date | Level of Harm | Residents Affected |
| Residential care facilities and facilities formerly licensed as residential care facilities II whose plans were initially approved between December 31, 1987 and December 31, 1998, shall have at least one (1) hydraulic or electric motor-driven elevator if there are more than twenty (20) residents with bedrooms above the first floor. The elevator installation(s) shall comply with all local and state codes, American Society for Mechanical Engineers (ASME) A17.1, Safety Code for Elevators, Dumbwaiters, and Escalators, and the National Fire Protection Association ' s applicable codes. All facilities with plans approved on or after January 1, 1999, shall comply with all local and state codes, ASME A17.1, 1993 Safety Code for Elevators and Escalators, and the 1996 National Electrical Code. These references are incorporated by reference in this rule and available at: American Society for Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990; and The American National Standards Institute, 11 West 42nd Street, 13th Floor, New York, NY 10036. This rule does not incorporate any additional amendments or additions. II
|
1/2/2024
| | |
| Exits, Stairways, and Fire Escapes.
(D) An " area of refuge " shall have-
1. An area separated by one- (1-) hour rated smoke walls, from the remainder of the building. This area must have direct access to the exit stairway or access the stair through a section of the corridor that is separated by smoke walls from the remainder of the building. This area may include no more than two (2) resident rooms;
2. A two- (2-) way communication or intercom system with both visible and audible signals between the area of refuge and the bottom landing of the exit stairway, attendants ' work area, or other primary location as designated in the written plan for fire drills and evacuation;
3. Instructions on the use of the area during emergency conditions that are located in the area of refuge and conspicuously posted adjoining the communication or intercom system;
4. A sign at the entrance to the room that states " AREA OF REFUGE IN CASE OF FIRE " and displays the international symbol of accessibility;
5. An entry or exit door that is at least a one and three-fourths inch (1 3/4") solid core wood door or has a fire protection rating of not less than twenty (20) minutes with smoke seals and positive latching hardware. These doors shall not be lockable;
6. A sign conspicuously posted at the bottom of the exit stairway with a diagram showing each location of the areas of refuge;
7. Emergency lighting for the area of refuge; and
8. The total area of the areas of refuge on a floor shall equal at least twenty (20) square feet for each resident who is blind or requires the use of a wheelchair or walker housed on the floor. II
|
10/18/2023
| | |
| Sprinkler Systems.
(A) Facilities licensed on or after August 28, 2007, or any section of a facility in which a major renovation has been completed on or after August 28, 2007, shall install and maintain a complete sprinkler system in accordance with NFPA 13, 1999 edition. I/II
|
10/18/2023
| | |
| Trash and Rubbish Disposal.
(A) Only metal or UL- or FM-fire-resistant rated wastebaskets shall be used for trash. II
|
10/18/2023
| | |
| In newly licensed facilities or if a new heating system is installed in an existing licensed facility, the heating of the building shall be restricted to steam, hot water, permanently installed electric heating devices or a warm air system employing central heating plants with installation such as to safeguard the inherent fire hazard, or approved installation of outside wall heaters which bear the approved label of the American Gas Association or National Board of Fire Underwriters. The foregoing requirements are applicable to residential care facilities. In assisted living facilities, the heating of the building shall be restricted to steam, hot water, permanently installed electric heating devices or a warm air system employing central heating plants with installation such as to safeguard the inherent fire hazard, or approved installation of outside wall heaters which bear the approved label of the American Gas Association or National Board of Fire Underwriters. For all facilities, oil or gas heating appliances shall be properly vented to the outside and the use of portable heaters of any kind is prohibited. If approved wall heaters are used, adequate guards shall be provided to safeguard residents. I/II
|
10/18/2023
| | |
| If extension cords are used, they must be Underwriters ' Laboratory (UL)-approved or shall comply with other recognized electrical appliance approval standards and sized to carry the current required for the appliance used. Only one (1) appliance shall be connected to one (1) extension cord and only two (2) appliances may be served by one (1) duplex receptacle. If extension cords are used, they shall not be placed under rugs, through doorways or located where they are subject to physical damage. II/III
|
10/18/2023
| | |
|
ICF2 |
10/18/2023
| | |